Honeywell UMC800 Reference Manual page 17

Rs232 communications
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

2.10.1 Read Contiguous 32-bit Values, continued
Response Message
Controller to Host: (good message)
Assume values are PV=1002.4, WSP = 1000.0, output = 10.4, and mode = 4.0 (Local SP, Automatic)
10 02 ff 01 01 09 02 04 44 7a 99 9a 44 7a 00 00 41 26 66 66 40 80 00 00 bf 40 10 03
DLE
STX
Dest i nation
Address
Source Address
Sequence N umber
Acknowledge
Contiguous 32 bit values
# of Values
PV = 1002.4
WSP = 1000.0
Output = 10.4
Mode = 4.0 (Local Setpoint, Auto Mode)
CRC
DLE
ETX
Mode is decoded as follows (also see Sect 2,48 of Manual 51-52-25-64):
0.0= RSP AUTO
1.0= RSP MAN
2.0= RSP Initialization Manual
3.0= RSP Local Override
4.0= LSP AUTO
5.0= LSP MAN
6.0= LSP Initialization Manual
7.0= LSP Local Override
Controller to Host (bad message, with a typical error code)
10|02|FF|01|0a|01|7e|80|10|03
8/99
RS232 Communications Reference Manual
Float ing Point IEEE Format
Protocol Description
7