Rtmr Function Block; Table 5-67 Rtmr Dynamic Parameters - Honeywell UMC800 Reference Manual

Rs232 communications
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Parameter Index Reference

5.53 RTMR Function Block

Description
The RTMR label stands for Resettable Timer. This block is part of the Counters/Timers category. It
looks like this graphically on the Control Builder.
Dynamic Parameters:
Parameter
Index
status
0
OUT
1
TIMER
2
RPRES
3
RST
4
EN
5
PREL
6
CNT_DN
7
98

Table 5-67 RTMR Dynamic Parameters

Type
Use
R/W
REAL
C
R
BOOL
O
R
REAL
O
R
REAL
I
R/W
BOOL
I
R
BOOL
I
R
REAL
I
R
BOOL
I
R
RS232 Communications Reference Manual
Description
block status
output
remaining time in seconds
Remote preset (0.0 – 99999.9)
if 'count-up' then represents Stop value in seconds
if 'count-down' then represents Start value in
seconds
OFF to ON transition, Reset
ENABLE
ON = run; timer is counting,
OFF = timer is stopped; output (TIMER) held at
last value
Preload:
if 'count-up' then represents Start value in seconds
if 'count-down' then represents Stop value in
seconds
(Range = 0.0 – 99999.9)
ON = count-down, OFF = count-up
8/99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs232

Table of Contents