Static Configuration Parameters:
Parameter
Index
GAIN
0
RATE
1
RESET
2
pv_hi
3
pv_lo
4
sp_hi_lim
10
sp_lo_lim
11
failsafe_hi
13
al_sp[4]
14-17
al_hyst
22
ATOUTHILIM
25
ATOUTLOLIM
26
FUZZY
27
TUNESET2
28
GAIN2
29
RATE2
30
RESET2
31
use_propband
32
8/99
BOOL
O
R
BOOL
O
R
REAL
O
R
BOOL
O
R
REAL
I
R
REAL
I
R
REAL
I
R
BOOL
I
R
REAL
I
R

Table 5-91 TPSC Static Configuration Parameters

Type
Description
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 1]
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 1]
REAL
integration time, 0.02 to 50 (minutes) or repeats per minute, 0.02 to 50
(repeats) [Tune Set 1]
REAL
pv High Range value –99999 to 99999 (default 100)
REAL
pv Low Range value –99999 to 99999 (default 0)
REAL
set point high limit, -99999 to 99999 (default 100)
REAL
set point low limit, -99999 to 99999 (default 0)
BOOL
ON sets motor to 100% when in failsafe. OFF sets motor to 0% (default
OFF)
REAL
alarm set points al1spl, al1sp2, al2spl, al2sp2, -99999 to 99999 (default
0)
REAL
alarm hysterysis 0 to 5 (%)
REAL
auto-tuning output high limit, 0% to 100%
REAL
auto-tuning output low limit, 0% to 100%
BOOL
ON enables fuzzy logic overshoot suppression (default OFF)
BOOL
Use tune set 2 (default OFF)
REAL
proportional gain, 0.1 to 1000 or proportional band, 0.1% to 1000%
[Tune Set 2]
REAL
derivative time, 0 or 0.1 to 10 (minutes) [Tune Set 2]
REAL
integration time, 0.02 to 50 (minutes) or repeats per minute, 50 to 0.02
(repeats) [Tune Set 2]
BOOL
Use Gain (0) or Proportional Band (1)
RS232 Communications Reference Manual
Function Parameter Index Reference
Alarm 1
Alarm 2
Back Calculation Out (%)
Auto Tune Indicator. ON = Auto Tune in progress
Process Variable Input (eu) (pv_lo <= PV <= pv_hi)
Remote Set Point (% or eu per sp_units)
Output Track Value (%)
Output Track Command {OFF, ON}
Remote bias value for ratio PID
123