Function Parameter Index Reference
5.51 ROC Function Block
Description
The ROC label stands for Rate of Change. This block is part of the Auxiliary category. It looks like this
graphically on the Control Builder.
Dynamic Parameters:
Parameter
Index
status
0
hi_rc
1
lo_rc
2
rate
3
IN
4
Static Configuration Parameters:
Parameter
Index
filt_time
0
range_hi
1
range_lo
2
direction_hi
3
direction_lo
4
hysteresis
5
96
Table 5-64 ROC Dynamic Parameters
Type
Use
R/W
REAL
C
R
BOOL
O
R
BOOL
O
R
REAL
O
R
REAL
I
R
Table 5-65 ROC Static Configuration Parameters
Type
Description
REAL
filter time constant
REAL
high rate of change setpoint
Range = 0 (off) to 99999.9 eu/min
REAL
low rate of change setpoint
Range = 0 (off) to 99999.9 eu/min
REAL
0 = both, 1 = increment only, 2 = decrement only
REAL
0 = both, 1 = increment only, 2 = decrement only
REAL
Range (0 – 999)
RS232 Communications Reference Manual
Description
block status
ON if rate > setpoint, else OFF
ON if rate < setpoint, else OFF
Rate of Change in EU/min
Analog Input
8/99