Function Parameter Index Reference
RESET2
32
use_propband
33
use_rpm
34
sp_rate_dn
35
sp_rate_up
36
FF_GAIN
37
RATIO
39
LBIAS
40
devbar_hi
41
devbar_low
42
92
REAL
integration time, 0 or 0.02 to 50 (minutes) or repeats per minute, 0
or 50 to 0.02 (repeats) [Tune Set 2]
BOOL
Use Gain (0) or Proportional Band (1)
BOOL
Use minutes (0) or repeats per minute (1) for integral constant
REAL
Set point low rate of change limit, 0 (off) to 99999 (eu/min)
REAL
Set point high rate of change limit, 0 (off) to 99999 (eu/min)
REAL
Feed forward gain, 0.0 to 10.0
REAL
Gain value for Ratio PID (-20 to 20) (default 1) [ used when
RA_BIAS > 0]
REAL
Bias value for Ratio PID when RA_BIAS = LOC_BIAS](-99999 to
99999) (0)
REAL
High scale value for deviation bar graph (0 to 99999) (default 100)
REAL
Low scale value for deviation bar graph [always = -devbar_hi]