5.43 ON/OFF Function Block

Description
The ON/OFF label stands for the On/Off Control function. This block is part of the Loops category. It
looks like this graphically on the Control Builder.
Dynamic Parameters:
Parameter
Index
status
0
lsp
1
lsp2
2
rem_mode
3
man_mode
4
man_out
5
rsp_eu
6
deviation
7
pv
8
WSP
9
OUT
10
MODE
11
All
12
AL2
13
BCO
14
PVI
15
RSP
16
TRV
17
TRC
18
8/99

Table 5-54 ON/OFF Dynamic Parameters

Type
Use
R/W
REAL
C
R
REAL
C
R/W
REAL
C
R/W
BOOL
C
R/W
BOOL
C
R/W
BOOL
C
R/W
REAL
C
R
REAL
C
R
REAL
C
R
REAL
O
R
BOOL
O
R
REAL
O
R
BOOL
O
R
BOOL
O
R
REAL
O
R
REAL
I
R
REAL
I
R
BOOL
I
R
BOOL
I
R
RS232 Communications Reference Manual
Function Parameter Index Reference
Description
block status (see section 5.2 for code list)
local set point (eu)
local set point 2 (eu)
remote set point mode request {OFF, ON}
manual output mode request {OFF, ON}
On/Off
remote set point in eu for monitoring
Deviation in eu for monitoring
Process Variable in eu for monitoring
Working Set Point in eu for monitoring
On/Off
actual mode encoded
Alarm 1
Alarm 2
Back Calculation Out (%)
Process Variable Input (eu) (pv_lo <= PV <=
pv_hi)
Remote Set Point (% or eu per sp_units)
On/Off
Manual On/Off