5.26 HLLM Function Block

Description
The HLLM label stands for High Low Limiter. This block is part of the Auxiliary category. It looks like
this graphically on the Control Builder:
Dynamic Parameters:
Parameter
Index
Type
status
0
REAL
OUT
1
REAL
H
2
BOOL
L
3
BOOL
X
4
REAL
Static Configuration Parameters:

Table 5-34 HLLM Static Configuration Parameters

Parameter
Index
Type
hilim
0
REAL
lolim
1
REAL
68

Table 5-33 HLLM Dynamic Parameters

Use
R/W
Description
C
R
block status (see section 5.2 for code list)
O
R
primary output
O
R
high limit indication
O
R
low limit indication
I
R
input
Description
high limit {-99999 to 999999} for Analog X value
low limit {-99999 to 999999} for Analog X value
RS232 Communications Reference Manual