Table 3-1. Analog Control Connector (J1), Designations And Functions - Ametek SPS A Series Operation Manual

Ametek sps a series dc power supplies
Table of Contents

Advertisement

Operation
Schematic
Symbol
*
22
IP RES
23
IP RTN
24
COM
25
IP RTN
Table 3–1. ANALOG CONTROL Connector (J1), Designations and Functions
Control ground is isolated from power ground with the isolated analog control (option). See
Section 3.3.1
*
Signals not available with isolated analog control (option).
CAUTION!
If standard analog programming is used, note the programming return (J1-6 &
J1-24) is at the same potential as the negative output terminal of the power
supply. Observance of return connections should be made with respect to input
programming signal equipment. Improper connection may result in ground loops
and as a result internal power supply damage may occur. (Output current then
flows to chassis by means of external connection to the J1 common (J1-6 &
J1-24)).
3-16
Electrical
Chars.
1 milliamp current source for remote current programming
~ 10.8V
using resistance. 0-5k ohm resistor referenced to Circuit
compliance
return Pin 23 or Pin 25 (IP RTN) will program the output
current from 0-100%. See Section 3.4.
Current programming return. Used with J1-10, J1-16 or
J1-22 and must be referenced to Pin 6 (COM) circuit
Zin ~ 10kΩ
common.
Circuit common. Electrically equal to Pin 6. Same potential
-
as the negative output terminal.
Current programming return. Used with J1-10, J1-16 or
J1-22 and must be referenced to Pin 6 (COM) circuit
Zin ~ 10kΩ
common.
AMREL SPS-A Series
Functional Description
M550129-01 Rev A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sga seriesSorensen sga seriesAmrel sps-a series

Table of Contents