IMO VXSM75-1 Instruction Manual page 66

Imo jaguar vxsm general purpose inverter
Table of Contents

Advertisement

1) Monitoring (monitoring of various data,
confirmation of function code data)
2) Frequency setting
3) Operation command (FWD, REV and
other commands set for digital input)
4) Function code data writing
Setting range: 0 to 3
The validity of communication can be switched
by a digital input. Set the link functions available
through communications.
Setting
Frequency
setting
0
Invalid
1
Valid
2
Invalid
3
Valid
The monitor function and function code data
writing function are always valid. When the
communication is disabled by means of a digital
input, a state similar to setting "0" is obtained.
H31
RS485 (address)
to
H39
RS485 (Response interval)
Set the various conditions of RS485
communication.
Set
specifications of the host unit. Refer to
section
9-4
for
specifications.
H31
Set the station address of RS485.
Setting range: 1 to 31
H32
RS485 (Mode select on no response
error)
Set the communication error handling
process and the error handling timer value.
Setting range: 0 to 3
Setting
Communication error handling process
0
Immediate Er 8 trip (coast to stop)
1
Operation continues until the timer time
elapses, then Er 8 trip.
2
Operation continues and retry is made
until the timer time elapses, then Er 8
trip upon a communication error or
continuation of operation upon no
communication error.
3
Operation continues.
Selecting Functions
Operation
command
Invalid
Invalid
Valid
Valid
according
to
the
protocol
and
other
H33
RS485 (Timer)
Set the error handling timer value.
Setting range: 0.0 to 60. 0 s
H34
RS485 (Baud rate)
Set the transmission speed.
Setting
Transmission speed
0
1 9 2 0 0 bit/s
1
9 6 0 0 bit/s
2
4 8 0 0 bit/s
3
2 4 0 0 bit/s
4
1 2 0 0 bit/s
H35
RS485 (Data length)
Set the data length.
Setting
Data lenght
0
8 bits
1
7 bits
H36
RS485 (Parity check)
Set the parity bit.
Setting
Parity bit
0
None
1
Even
2
Odd
H37
RS485 (Stop bits)
Set the stop bit.
Setting
Stop bit
0
2bits
1
1bit
H38
RS485 (No response error detection
time)
In a system where there is always an access
to the station at certain intervals, no access
caused by broken wire or other errors is
detected and the inverter trips in Er8.
Setting range:
0 to 60 s
0: No detection
H39
RS485 (Response interval)
Set the time taken until a response is sent
back to the host unit upon a request.
Setting range: 0.00 to 1.00 s
5-37