C: Control Functions of Frequency
C01
C01 Jump frequency 1
C02
C02 Jump frequency 2
C03
C03 Jump frequency 3
C04
C04 Jump frequency hysteresis
These functions jump the inverter output
frequency at the set frequencies to avoid
mechanical resonance with the load.
Three jump frequencies can be set.
This function is inactive when all the jump
frequencies 1 through 3 are set at 0 Hz.
The frequencies are not jumped during
acceleration or deceleration.
If the setting ranges of jump frequencies
overlap, the sum of the setting ranges is
jumped.
C01
C02
C03
Setting range: 0 to 400 Hz
Minimum unit: 1 Hz
C04
Setting range: 0 to 30 Hz
Minimum unit: 1 Hz
5-26
C05
Multistep frequency 1 through
C19
Multistep frequency 15
Terminal functions SS1, SS2, SS4 and SS8
are turned on or off to switch multistep
frequencies 1 through 15. (Refer to E01
through E05 for the definition of the terminal
function.)
Undefined
terminals
functions SS1, SS2, SS4 and SS8 are
assumed to be turned off.
Setting range: 0.00 to 400.0 Hz
Minimum unit: 0.01 Hz
among
terminal
Selecting Functions