9-4-11 Function Code List

The function code includes the function codes
indicated in chapter 5 "Selecting Functions" and
the following functions for the standard and
short frames.
(1)Functions for standard frame (command
data)
Name
Command
type
Reset command
E
Frequency and
R/W
speed command
Frequency
R/W
command
Operation
R/W
command
Acceleration time 1
R/W
Deceleration time 1 R/W
Torque limit level 1 R/W
Torque limit level 2 R/W
Table 9-4-5 Standard frame (command data)
Notes)
1) Negative values are set in 2's complements.
2) When reading S01 or S05, the data
commanded via communication is read out
instead of the command value in the actual
operation. To read the actual command
value, read the monitor data.
3) If both S01 and S05 are designated (written
with data other than zero), the S01 command
Specifications
Function type
Data and operation
character and
number
3 spaces
Space is transmitted in the data field. The function
resets a protective operation (tripping).
S01
±20000d/fmax (Max. frequency)
S05
0.00 to 400.00 Hz / 0 to 40000 (100 times value)
The inverter operates at the maximum frequency
even if a value larger than the maximum frequency is
set by function code F03.
A communication command is read in the reading
mode.
S06
bit15:RESET 1:ON,0:OFF
bits 14 to 7: Fixed to 0
bit6:X5 1:ON,0:OFF
bit5:X4 1:ON,0:OFF
bit4:X3 1:ON,0:OFF
bit3:X2 1:ON,0:OFF
bit2:X1 1:ON,0:OFF
bit 1: REV (reverse rotation command) 1:ON,0:OFF
bit 0: FWD (forward rotation command) 1:ON,0:OFF
X1, X2, X3, X4 and X5 function according to function
code E01 to E05 settings.
S08
0.0~3600.0s/0~36000
(Value multiplied by 10)
S09
0.0~3600.0s/0~36000
(Value multiplied by 10)
S10
100% (rated torque) / + 10000
(Value multiplied by 100)
S11
100% (rated torque) / + 10000
(Value multiplied by 100)
is effective.
4) For the alarm input, "0" indicates a failure.
5) X1 through X5 are used for general purpose
inputs; set the function of each terminal using
the general input terminal setting of the
inverter.
6) To cancel the torque limit of S10 and S11,
send 7FFFH.
9-20