Applicable Devices And Cable Sizes For Main Circuit - IMO VXSM75-1 Instruction Manual

Imo jaguar vxsm general purpose inverter
Table of Contents

Advertisement

2-3-5 Applicable Devices and Cable Sizes for Main Circuit

Nominal
Inverter
applied
type
motor
[kW]
VXSM40-1
VXSM75-1
VXSM150-1
VXSM220-1
VXSM40-3
VXSM75-3
VXSM150-3
VXSM220-3
VXSM400-3
VXSM550-3
VXSM750-3
Table 2-3-4 Selection of peripheral devices
*1 The applicable frame and series of the model of
the molded case circuit breaker (MCCB) and
earth leakage breaker (ELCB) vary according to
the capacity of the transformer of the equipment.
For details of selection, refer to the relevant
technical documents.
*2 The recommended cable size for the main circuit
is PVC cable at ambient temperature 40 degree
C specified in Appendix C of EN 60204
*3 The power supply impedance without a reactor
is considered to be the equivalent of 0.1% of the
inverter capacity, with 10% current unbalance
accompanied by the voltage unbalance.
*4 Use crimp terminals with an insulating cover.
2-11
Molded case circuit
breaker (MCCB) or
earth leakage
circuit breaker
(ELCB) *
1
Rated current [A]
With
Without
DCR
reactor*
0.4
6
10
0.75
10
16
1.5
16
25
2.2
25
32
0.4
6
0.75
6
1.5
10
2.2
10
16
4.0
5.5
16
25
7.5
20
32
Recommended wire size [mm
Input circuit*
2
[L1/R,L2/S,L3/T]
circuit*
[L1/L, L2/N]
[U, V, W]
G
With
Without
3
DCR
reactor*
3
2.5
2.5
4
4
6
2.5
2.5
4
6
2
]
Output
DCR*
2
2
circuit
Control
[P1]
wiring
[P(+)]
DB
2.5
0.5
2.5
2.5
(DB)
4
(Others)
2.5
2.5
0.5
Installation and Connection

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents