5-2

Detail Description of Each

Function

F: Fundamental functions
F00
Data protection
The setting data can be protected against
inadvertent operation at the keypad panel.
0: Data change enabled
1: Data protected
[Setting method]
0¡1: Press the
+
STOP
1¡0: Press the
+
V
STOP
F01
Frequency command 1
The frequency setting method can be
selected.
0: The frequency is set by the operation of
and
keys.
V
1: The frequency is set by the voltage input
(at terminal 12) (0 to +10 Vdc).
2: The frequency is set by the current input (at
terminal C1) (4 to 20 mAdc).
3: The frequency is set by the voltage input
and current input (terminal 12 and terminal
C1) ((-10 to +10 Vdc) + (4 to 20 mAdc)).
Inputs at terminals 12 and C1 are added to
determine the frequency.
4: The frequency is set by the voltage input with
polarity (at terminal 12) (-10 to +10 Vdc).
In the case of input with polarity, operation
at a direction opposite to the operation
command is possible.
5: The frequency is set by voltage input
inverse mode operation (at terminal 12)
(+10 to 0 Vdc).
6: The frequency is set by current input
inverse mode operation (at terminal C1) (20
to 4 mAdc).
7: UP/DOWN control mode 1
The frequency is set by terminal UP,
terminal DOWN. (initial value = 0)
8: UP/DOWN control mode 2
The frequency is set by terminal UP,
terminal DOWN (initial value = last value
during previous operation).
Refer to the description of the E01 to E05
functions for details.
F02
Operation method
The operation input method is set. (Note:
This function can be changed only when the
FWD and REV terminals are open.)
0: The motor starts or stops upon keypad
operation (
or
RUN
STOP
Selecting Functions
keys simultaneously.
keys simultaneously.
I
key).
Description of forward and reverse operation
The direction of rotation is determined by
the FWD and REV terminals on the control
terminal block as follows.
FWD-P24 short-circuited:Forward rotation
REV-P24 short-circuited: Reverse rotation
The motor does not start if both the FWD
and REV terminals are connected with the
P24 terminal or both of them are open.
1: External signal (digital input)
The motor starts or stops upon the state of
the FWD and REV terminals on the control
terminal block.
FWD-P24 short-circuited:forward rotation
REV-P24 short-circuited: reverse rotation
The motor does not start if both the FWD
and REV terminals are connected with the
P24 terminal or both of them are open.
2: Keypad operation (forward rotation only)
The motor runs in the forward direction
when the
key is pressed and it
RUN
decelerates to stop when the
pressed.
3: Keypad operation (reverse rotation only)
The motor runs in the reverse direction
when the
RUN
decelerates to stop when the
pressed.
Normal mode operaton
(setting: 1.3,4
Inverse mode operaton
(setting: 5
Normal mode operaton
(setting: 2
Inverse mode operaton
(setting: 5
key is
STOP
key is pressed and it
key is
STOP
5-11