H21
PID control (Feedback signal)
Select the feedback value input terminal and
electrical specification of the terminal. Select
one from the table below according to the
specifications of the sensor.
Setting
Selection item
0
Control terminal 12, normal
operation (voltage input 0 to +10V)
1
Control terminal C1, normal
operation (current input 4 to 20 mA)
2
Control terminal 12, inverse
operation (voltage input +10 to 0V)
3
Control terminal C1, inverse
operation (current input 20 to 4 mA)
H22
PID control (P (P gain))
Generally speaking, P: gain, I: integral time
and D: differential time are not used alone.
Functions are combined like: P control, PI
control, PD control and PID control.
P action
An operation where there is proportional
relationship between the amount of operation
(output frequency) and deviation is called P
operation. Therefore the P action outputs an
operation
amount
deviation. However, the deviation cannot be
eliminated by only the P action.
Setting range: 0.01 to 10.00 times
5-34
proportional
to
the
Note) The feedback value of the PID control
can be input only in the positive polarity.
The negative polarity (0 to -10 Vdc, -10
to 0 Vdc, etc.) cannot be input. Therefore
the control cannot be applied to
reversible operation using the analog
signal.
The P gain is a parameter which determines
the degree of response to the deviation of P
action. With a large gain, the response is
quick but hunting is likely to occur. With a
small gain, the response is stable but slow.