F15
Frequency limiter (High)
F16
Frequency limiter (Low)
Set the upper and lower limits of the
frequency setting.
Setting range: 0 to 400 Hz
*The starting frequency is output when the
inverter starts operation, and the stopping
frequency is output when it stops operation.
*(Low limit) > (High limit)...Priority is given to the
High limit value.
F17
Gain (Frequency setting signal)
Set the ratio of the frequency setting in
relation to the analog input.
The operation is as shown in the figure below.
CAUTION
The brake function of the inverter
does not insure the function of a
mechanical latch.
Injuries could occur.
Selecting Functions
F18
Bias frequency
This function obtains the frequency setting
from addition of the frequency setting in
relation to the analog input and a bias
frequency. The operation is as shown in the
figure below.
However, if the bias frequency is larger
(smaller) than the maximum frequency (-
maximum frequency), the limit is set at the
maximum output frequency (- maximum
output frequency).
F20
DC brake (Starting frequency)
F21
DC brake (Braking level)
F22
DC brake (Braking time)
F20
Starting frequency: Set the frequency at
which the DC brake starts operation during
deceleration and stop.
Setting range: 0.0 to 60.0 Hz
F21
Braking level: Set the output current level
during DC braking. The level can be set in an
increment of 1% of the rated inverter output
current.
Setting range: 0 to 100%
Actual minimum level is fixed to 5% even if
this function set from 1 to 5% for
VXSM75-1/550-3.
F22
Braking time: Set the operation time of DC
braking.
Setting range:
0.0 Inactive
0.1 to 30.0 s
5-17