IMO VXSM75-1 Instruction Manual page 60

Imo jaguar vxsm general purpose inverter
Table of Contents

Advertisement

I Upon success of retry
I Upon failure of retry
H06
Fan stop operation
With this function, the temperature of the heat
sink is detected while the inverter is turned
on, to turn on or off the cooling fan
automatically. If this function is not selected,
the cooling fan rotates at all times.
Setting 0: No on/off control
1: On/off control (thermostat)
H07
ACC/DEC pattern (Mode select)
Select the acceleration/deceleration mode.
Setting 0: Inactive
(linear acceleration/deceleration)
1: S-curve acceleration/deceleration
(Weak)
2: S-curve acceleration/deceleration
(Strong)
3: Non-linear (for variable torque)
When the function is set at "1", "2" or "3", a
change in the acceleration or deceleration time
during acceleration or deceleration is not
reflected immediately. The setting becomes
effective after a constant speed is reached or
the inverter is stopped.
Selecting Functions
[S-curve acceleration/deceleration]
To reduce the shock of the mechanical system,
the change in the output frequency is made
smooth when the frequency is set.
α
α
β
β
<Constant of each pattern>
H07 = 1
(slow S-curve
pattern)
Range of
0.05 x
S-curve
(Maximum
(α)
output
frequency [Hz])
S-curve
0.10 x
time
(Acceleration
during
time [s])
acceleration
on (ßacc)
S curve
0.10 x
time
(Deceleration
during
time [s])
deceleration
on (ßacc)
When the acceleration/deceleration time is
extremely long or short, the result is linear
acceleration/deceleration.
[Curved acceleration/deceleration]
Use
this
option
acceleration/deceleration
acceleration/deceleration pattern of the motor
including the operation zone in the constant
output range.
β
β
H07 = 2
(steep S-curve
pattern)
(Maximum
frequency [Hz])
0.20 x
(Acceleration
time [s])
0.20 x
(Deceleration
time [s])
to
minimize
the
time
for
an
5-31

Hide quick links: