Zero Return Function
This function performs two types of zero return operations according to Zero Return Mode
(P068).
Zero return starts when the Zero return start signal (70: ORG) turns ON. When zero return is
complete, the current position is cleared (= 0).
Select the zero return direction in Zero Return Direction Selection (P069).
If zero return is not performed, the Inverter performs position control with the position at power-
on defined as the origin.
force.)
Reference
When using the zero return function (mode 1 or 2), set P075 (Positioning Mode Selection) to 00 (limit).
Parameter
No.
P068
P069
P070
P071
C001 to C007
Zero Return Mode 1 (P068 = 00)
ORG input
ORL input
Output
frequency
(1) Accelerate until the zero return mode 1 frequency (speed) according to the acceleration time.
(2) Operate at the zero return mode 1 frequency (speed).
(3) Apply DC injection braking (DB) the moment an ORL signal is input.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Function name
00: Zero return mode 1
Zero Return Mode
01: Zero return mode 2
00: Forward side
Zero Return
Direction Selection
01: Reverse side
Zero Return Mode 1
0.00 to 10.00 (100.0)
Frequency
Zero Return Mode 2
0.00 to 400.0
Frequency
69: ORL (Zero return limit signal)
Multi-function Input
Selection
70: ORG (Zero return startup signal)
ON
(2)
Zero Return Mode 1 Frequency (P070)
(1)
(3) DB
Zero
5-12 Simple Position Control Function
Data
ON
Position
Default
Unit
setting
−
00
01
−
5.00
Hz
5.00
Hz
−
−
5-168
5