Torque Ladstop Function - Omron 3G3MX2 User Manual

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

5-11 Sensorless Vector Control

Torque LADSTOP Function

This function temporarily stops the frequency deceleration function (LAD) when the torque limit
function is actuated. This function is enabled only when Sensorless Vector Control is selected
for control method (A044/A244 = 03).
Parameter
b045
Output frequency
TRQ output
5
5-155
Function name
No.
Torque LADSTOP
Selection
Related functions
Data
00: Disabled
01: Enabled
A044/A244, b040, b041to b044
Torque limit in progress (during torque limit)
Time
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Default
Unit
setting
00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents