Wire Sizes for Control Circuit Terminal Block and Relay Output Terminal Block
Relay output
terminal block
Control Circuit Terminal
Block
Relay output terminal
block
Recommended Terminal
To improve the ease of wiring and reliability of connection, use of ferrules of the following
specifications is recommended for signal wires:
Wire size
2
mm
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
0.75 (18)
* Manufacturer: Phoenix Contact
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Single wire mm
(AWG)
0.2 to 1.5
(AWG 24 to 16)
0.2 to 1.5
(AWG 24 to 16)
Ferrules
L [mm]
type*
AI 0.25-8YE
12.5
AI 0.34-8TQ
12.5
AI 0.5-8WH
14
AI 0.75-8GY
14
Crimp tool CRIPMFOX UD 6-4 or CRIMPFOX ZA 3
Control circuit terminal block
8 mm
Stripping length for
single/stranded wires:
Approx. 8 mm
Applicable wire
2
2
Stranded wire mm
(AWG)
0.2 to 1.0
(AWG 24 to 17)
0.2 to 1.0
(AWG 24 to 17)
φd [mm]
φD [mm]
0.8
2.0
0.8
2.0
1.1
2.5
1.3
2.8
2-2 Wiring
2
Ferrules mm
(AWG)
0.25 to 0.75
(AWG 24 to 18)
0.25 to 0.75
(AWG 24 to 18)
φd
8
L
φD
2-20
2