Register
Function name
No.
0044h
Fault Monitor 6: Cause
Fault Monitor 6:
0045h
Inverter Status
Fault Monitor 6:
0046h
Frequency (HIGH)
Fault Monitor 6:
0047h
Frequency (LOW)
Fault Monitor 6:
0048h
Current
Fault Monitor 6:
0049h
Voltage
Fault Monitor 6: RUN
004Ah
Time (HIGH)
Fault Monitor 6: RUN
004Bh
Time (LOW)
Fault Monitor 6: ON
004Ch
Time (HIGH)
Fault Monitor 6: ON
004Dh
Time (LOW)
004Eh Warning Monitor
004Fh
to
Not used
08FFh
0900h
EEPROM Write
0901h
Not used
EEPROM Write Mode
0902h
Selection
0903h
to
Not used
1000h
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
6-8 List of Modbus Communication (Modbus-RTU) Data
Parameter
R/W
No.
d086
R
d090
R
W
W
Monitor and setting
parameters
Refer to "Inverter Fault Factor
List" on page 6-35.
Refer to "Inverter Fault Factor
List" on page 6-35.
0 to 100000
Output current value at the
time of tripping
DC input voltage at the time of
tripping
Total RUN time at the time of
tripping
Power ON time at the time of
tripping
Warning code
Inaccessible
0: Motor parameter
recalculation
1: Set value storage in
EEPROM
Other: Motor parameter
recalculation and set
value storage in
EEPROM
Inaccessible
0: Write disabled
1: Write enabled
Inaccessible
Data
resolution
0.01 [Hz]
0.01 [A]
0.1 [V]
1 [h]
1 [h]
6