Exceptional Response - Omron 3G3MX2 User Manual

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Exceptional Response

The master requests the response for a query other than broadcast or broadcast to each
group. Though the Inverter should return a response corresponding with the query, it returns
an exceptional response if the query has an error.
The exceptional response has the field configuration shown in the following table.
Slave address
Parameter No.
Exceptional code
Error check
The detailed field configuration is shown in the table below. The Parameter No. of the
exceptional response will be the value of the query Parameter No. to which 80h is added. The
exceptional code shows the cause of exceptional response.
Exceptional
* UV: During undervoltage
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Field Configuration
Parameter No.
Query
Exceptional response
01h
81h
03h
83h
05h
85h
06h
86h
0Fh
8Fh
10h
90h
17h
97h
code
01h
Specified an unsupported function.
02h
Specified address does not exist.
03h
Specified data has an unacceptable format.
21h
Data is out of setting range for writing into the holding register.
The Inverter does not allow this function.
Has attempted to change the register that cannot be changed
during operation.
Has issued the enter command during operation (UV*).
Has written into the register during trip (UV*).
Has written into a soft-locked register.
22h
Has attempted to change an I/O terminal that cannot be changed.
Has attempted to change the contact type of the RS (reset)
allocation terminal.
Has attempted to write into a register when auto-tuning was
enabled.
Has attempted to write into a locked register while a password was set.
23h
Has written into the read-only register (coil).
6-5 Explanation of Each Parameter No.
Description
6
6-18