Omron 3G3MX2 User Manual page 297

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

The following table gives the differences in the setting ranges and default
settings for parameters in Normal Mode with a Heavy Load Rating (CT) and
High-frequency Mode.
Parameter
Function name
No.
F002
Acceleration Time
Setting 1
F202
Acceleration Time
Setting 2
F003
Deceleration Time
Setting 1
F203
Deceleration Time
Setting 2
A003
Base Frequency 1
A203
Base Frequency 2
A004
Maximum
Frequency 1
A204
Maximum
Frequency 2
A011
FV Start Frequency 0.00 to 400.00 [Hz]
A012
FV End Frequency
A044
Control Method 1
A244
Control Method 2
A059
DC Injection
Braking Carrier
Frequency
A063
Jump Frequency 1
A064
Jump Frequency
Width 1
A065
Jump Frequency 2
A066
Jump Frequency
Width 2
A067
Jump Frequency 3
A068
Jump Frequency
Width 3
A069
Acceleration Stop
Frequency
A092
1st Acceleration
Time 2
A292
2nd Acceleration
Time 2
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Normal Mode with a Heavy Load
Rating (CT)
Setting range
0.01 to 3,600.00 [s]
0.01 to 3,600.00 [s]
0.01 to 3,600.00 [s]
0.01 to 3,600.00 [s]
30.0 to Maximum Frequency
1 (A004) [Hz]
30.0 to Maximum Frequency
2 (A204) [Hz]
Base Frequency 1 (A003) to
400.0 [Hz]
Base Frequency 2 (A203) to
400.0 [Hz]
0.00 to 400.00 [Hz]
00: VC
01: VP 1.7th power <VC, if low
speed>
02: Free V/f setting
03: Sensorless vector control
00: VC
01: VP 1.7th power <VC, if low
speed>
02: Free V/f setting
03: Sensorless vector control
2.0 to 15.0 [kHz]
0.00 to 400.00 [Hz]
0.00 to 10.00 [Hz]
0.00 to 400.00 [Hz]
0.00 to 10.00 [Hz]
0.00 to 400.00 [Hz]
0.00 to 10.00 [Hz]
0.00 to 400.00 [Hz]
0.01 to 3,600.00 [s]
0.01 to 3,600.00 [s]
5-14 Other Functions
High-frequency Mode
Default
Setting range
10.00
0.01 to 3,600.00 [s]
10.00
0.01 to 3,600.00 [s]
10.00
0.01 to 3,600.00 [s]
10.00
0.01 to 3,600.00 [s]
60.0
30.0 to Maximum Frequency
1 (A004) [Hz]
60.0
30.0 to Maximum Frequency
2 (A204) [Hz]
60.0
Base Frequency 1 (A003) to
1,000.0 [Hz]
60.0
Base Frequency 2 (A203) to
1000.0 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
00
00: VC
01: VP 1.7th power <VC, if
low speed>
02: Free V/f setting
00
00: VC
01: VP 1.7th power <VC, if
low speed>
02: Free V/f setting
5.0
2.0 to 10.0 [kHz]
0.00
0.00 to 1,000.00 [Hz]
0.50
0.00 to 100.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.50
0.00 to 100.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.50
0.00 to 100.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
10.00
0.01 to 3,600.00 [s]
10.00
0.01 to 3,600.00 [s]
Default
30.00
30.00
30.00
30.00
1000.0
1000.0
1000.0
1000.0
5
0.00
0.00
00
00
5.0
0.00
0.50
0.00
0.50
0.00
0.50
0.00
15.00
15.00
5-180

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3G3MX2 and is the answer not in the manual?

Table of Contents

Save PDF