7-1 Error Display and Remedial Actions
Brake error
Emergency
shutoff
Overload
protection in a
low speed
range
Poor Digital
Operator
connection
Modbus
communication
(Modbus-RTU)
error
7
Internal data
error
Option error
Option timeout
7-5
Name
Description
A trip will occur if brake ON/OFF cannot
be confirmed within the Brake
Confirmation Wait Time (b124) after the
Inverter has issued a brake release
output, provided that the Brake Control
function is enabled (b120 = 01).
*1
If an overload occurs in the extremely
low speed range of 0.2 Hz or below, it
will be detected by the built-in
electronic thermal of the Inverter and a
trip will occur. (However, the error
history may indicate a high frequency).
The Inverter is tripped when there is an
error or broken line for communications
with an externally connected Operator
(optional).
A trip will occur upon timeout if the
communication error selection is set to
tripping (C076 = 00).
This error is reported by an optional
board.
A timeout occurred in communications
between the Inverter and optional
board, and the Inverter was tripped.
Error
Check point and remedy
code
E36.
Is the brake ON/OFF function
working?
→Check the brake.
Is the set time for b124 too
short?
→Increase b124 .
Has the brake confirmation
signal been input?
→Check the wiring.
E37.
E38.
Is the load too large?
→Decrease the load rate.
E40.
Is there a communications
error?
→Check the cable and
replace it if necessary.
This error will not be
detected if b165 is set to
02 (ignore).
E41.
Is the communication speed
correct?
→Check the setting.
Is the wiring distance
appropriate?
→Check the
communication wiring.
Has disconnection occurred?
→Check the wiring.
E43. to
E59.
E60. to
Refer to the manual for the
E68.
optional board for details.
E69.
The optional board is
disconnected.
→Check to see if the case
of the optional board is
mating properly with the
Inverter. Tighten the
mounting screws.
The option board is
malfunctioning.
→If the optional board is
mated properly, it may have
failed.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)