Omron 3G3MX2 User Manual page 298

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

5-14 Other Functions
Parameter
No.
A093
A293
A095
A295
A096
A296
A101
A102
A145
A154
5
A156
A161
A162
b007
b019
b054
b082
b083
b112
C027
5-181
Normal Mode with a Heavy Load
Function name
Setting range
1st Deceleration
0.01 to 3,600.00 [s]
Time 2
2nd Deceleration
0.01 to 3,600.00 [s]
Time 2
2-step Acceleration
0.00 to 400.00 [Hz]
Frequency 1
2-step Acceleration
0.00 to 400.00 [Hz]
Frequency 2
2-step
0.00 to 400.00 [Hz]
Deceleration
Frequency 1
2-step
0.00 to 400.00 [Hz]
Deceleration
Frequency 2
FI Start Frequency
0.00 to 400.00 [Hz]
FI End Frequency
0.00 to 400.00 [Hz]
Frequency Addition
0.00 to 400.00 [Hz]
Amount Setting
Deceleration Stop
0.00 to 400.00 [Hz]
Frequency
PID Sleep Function
0.00 to 400.00 [Hz]
Operation Level
VR Start
0.00 to 400.00 [Hz]
Frequency
VR End Frequency
0.00 to 400.00 [Hz]
Frequency
0.00 to 400.00 [Hz]
Matching Lower
Limit Frequency
Setting
Free-electronic
Free-electronic Thermal
Thermal
Frequency 2 to 400 [Hz]
Frequency 3
Freq. Drop to Start
0.00 to 10.00 [Hz]
Ctrl. Decel
Starting Frequency
0.10 to 9.99 [Hz]
Carrier Frequency
2.0 to 15.0 [kHz]
Free V/f Frequency
Free V/f Frequency 6 to 400
7
[Hz]
MP Selection
00: Output frequency
01: Output current
02: Output torque
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load
rate
07: LAD frequency
08: Digital current monitor
10: Cooling fin temperature
12: Do not use this setting.
15: Pulse train input monitor
16: Optional board
Rating (CT)
Default
10.00
0.01 to 3,600.00 [s]
10.00
0.01 to 3,600.00 [s]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.00
0.00 to 1,000.00 [Hz]
0.0
Free-electronic Thermal
Frequency 2 to 1,000 [Hz]
0.00
0.00 to 100.00 [Hz]
0.50
0.10 to 100.00 [Hz]
10.0
2.0 to 10.0 [kHz]
0.
Free V/f Frequency 6 to
1,000 [Hz]
07
00: Output frequency
01: Output current
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load
rate
07: LAD frequency
08: Digital current monitor
10: Cooling fin temperature
12: Do not use this setting.
15: Pulse train input monitor
16: Optional board
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
High-frequency Mode
Setting range
Default
15.00
15.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.0
0.00
0.50
5.0
0.
07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents