Omron 3G3MX2 User Manual page 296

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

5-14 Other Functions
Major Differences between High-frequency Mode and Normal Mode
Heavy Load/Light Load
Selection (b049)
Maximum Frequency
(A004)
Starting Frequency
(b082)
Carrier Frequency
(b083)
Control Method (A044)
Acceleration Pattern
Selection (A097)
Deceleration Pattern
Selection (A098)
5
Automatic Carrier
Reduction (b089)
Note: In the high-frequency mode, the values are fixed and thus parameters b049, A097, A098 and b089
5-179
High-frequency
Function name
Heavy load rating (CT) Heavy load rating (CT)
1000 [Hz]
0.10 to 100.0 [Hz]
2.0 to 10.0 [kHz]
00: Constant torque
characteristics
01: Reduced torque
characteristics
02: Free V/f setting
00: Line
00: Disabled
are not displayed.
mode
400 [Hz]
0.10 to 9.99 [Hz]
2.0 to 15.0 [kHz]
00: Constant torque
characteristics
01: Reduced torque
characteristics
02: Free V/f setting
03: Sensorless vector
control
00: Linear
01: S shape curve
02: U shape curve
03: Reverse-U shape
curve
04: EL-S shape curve
00: Disabled
01: Enabled, depends on
current
02: Enabled, depends on
fin temperature
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Normal mode
Light load rating (VT)
400 [Hz]
0.10 to 9.99 [Hz]
2.0 to 10.0[kHz]
00: Constant torque
characteristics
01: Reduced torque
characteristics
02: Free V/f setting
00: Linear
01: S shape curve
02: U shape curve
03: Inverted U shape
curve
04: EL-S shape curve
00: Disabled
01: Enabled, depends
on current
02: Enabled, depends
on fin temperature