2-2 Wiring
Wiring Example (Sink Logic)
RS+
2
When connecting a relay to the multi-function output terminal, install a surge-absorbing diode
in parallel with the relay. The output circuit can break down due to surge voltage when the relay
is switched on/off.
Switching Method for Input Control Logics
Multi-function input terminals are set to sink logic at the factory.
To switch the input control logic to source logic, remove the shorting bar between terminals
P24 and PSC on the control circuit terminal block, and connect it between terminals PSC and
SC.
(1) Sink logic
S2
2-19
RS−
S7/EB
S6
S5/TH S4/GS2 S3/GS1
MP
RP
FS
FV
Variable Resistor
Frequency reference
(1 to 2 kΩ)
S1
SC
PSC P24
Shorting bar
Communication
Relay output
MB MA MC
Communication
RS-485
S2
S1
FI
SC
AM
PC
Signal during
RUN
Frequency reading
(2) Source logic
S2
S1
SC
PSC P24
Shorting bar
Logic input
RS-485
RS− S7
S5
S4
S6
/EB
/TH
/GS2
RS+ MP
RP
FS
FV
Pulse
Pulse
Analog input and
output
input
power supply
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Shorting bar
(sink logic)
SC
PSC
P24
P2
P1/EDM
RY
RY
Frequency arrival
signal
(27 VDC 50 mA max.)
Logic common and
power supply
S3
S2
S1
SC
PSC P24
/GS1
P1
FI
SC
AM PC
P2
/EDM
Analog
Logic output
output
Shorting
bar

Hide quick links: