Integrated Management Module Ii (Imm2) Error Messages - IBM System x3530 M4 Installation And Service Manual

Type 7160
Hide thumbs Also See for System x3530 M4:
Table of Contents

Advertisement

v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
v Go to the IBM support website at http://www.ibm.com/supportportal/ to check for technical information, hints,
tips, and new device drivers or to submit a request for information.
Diagnostic
code
Message
W.3818005 [W.3818005] The CRTM flash
driver could not successfully
flash the staging area. The
update was aborted.
S.3818007 [S.3818007] The firmware image
capsules for both flash banks
could not be verified.
W.3938002 [W.3938002] A boot
configuration error has been
detected.

Integrated management module II (IMM2) error messages

The following table describes the IMM2 error messages and suggested actions to
correct the detected problems.
For more information about IMM2, see the Integrated Management Module II User's
Guide at http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-
5086346.
Table 13. IMM2 error messages
v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
Event ID
Message
Temperature and fan messages
80010701-0701xxxx
Numeric sensor
adapter Ambient
Temp going high
(upper non-critical)
has asserted.
80010701-0c01xxxx
Numeric sensor
Ambient Temp going
high (upper
non-critical) has
asserted.
140
System x3530 M4 Type 7160: Installation and Service Guide
Description
CRTM Update Aborted.
CRTM image capsule could not
be verified.
Boot Configuration Error.
Severity
Description
Warning
An upper
non-critical sensor
going high has
asserted.
Warning
An upper
non-critical sensor
going high has
asserted.
Action
1. Run the Setup utility, select Load
Default Settings, and save the
settings.
2. Recover the server firmware.
1. Run the Setup utility, select Load
Default Settings, and save the
settings.
2. Recover the server firmware.
1. Run the Setup utility, select Load
Default Settings, and save the
settings.
2. Recover the server firmware.
Action
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.