Using Event Inputs
4-5-3

Settings

Switching between Set Points 0, 1, 2, and 3
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input type
in-t
5
amov
-169
Advanced Function Setting Level
Parameter
init
initialization
off
Number of Multi-SP Uses Setting
Number of
ev-m
multi-SP uses
1
ev-m
2
4-5-4

Executing Run/Stop Control

The following example sets the "number of multi-SP uses" parameter to 2.
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the "move to advanced function setting level" parameter by press-
ing the M key.
3. Use the D key to enter " 169" (the password).
Move to the advanced function setting level by pressing the M key or
leaving the setting for at least two seconds.
4. Select the "number of multi-SP uses" parameter by pressing the M key.
5. Use the U key to set the parameter to 2.
6. To return to the initial setting level, press the O key for at least one sec-
ond.
7. To return to the operation level, press the O key for at least one second.
Set points 0, 1, 2 and 3 will be set according to the ON/OFF states of event
inputs 1 and 2.
E5CN
EV1
EV1
EV2
+
EV2
+
When the "event input assignment 1" or "event input assignment 2" parameter
is set to STO (RUN/STOP), control is started when event input 1 or 2 turns
OFF. Control is stopped when the input turns ON. Alarm outputs, however, will
be according to the process value.
The STOP indicator will light while control is stopped.
Setting
Event input 1 or 2
Event input 1 or 2
E5AN/EN
EV1
+
EV1
+
EV2
EV2
Input contact
ON
OFF
Section 4-5
Status
STOP
RUN
79