Advanced Function Setting Level
prlt
Move to Protect Level Time
Function
Setting
See
See
sero
Input Error Output
Function
Setting
cjc
Cold Junction Compensation Method
Function
Setting
See
See
168
• This parameter sets the key pressing time required to move to the protect
level from the operation level or the adjustment level.
Setting range
1 to 30
Second
■ Related Parameters
Operation/adjustment protect, initial setting/communications protect, setting
change protect (protect level): Page 116
• When this parameter is set to ON, alarm 1 output turns ON for input
errors.
The alarm 1 operation indicator will not light.
• The alarm 1 output is an OR output of alarm 1, HBA burnout/HS alarm,
and input error.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Setting range
on: Enabled, off: Disabled
• Specifies whether cold junction compensation is to be performed inter-
nally by the Controller or to be performed externally when the input type
setting is to between 5 and 22.
• The cold junction compensation external setting is enabled when the tem-
perature difference is measured using two thermocouples or two ES1B
Sensors.
Setting range
on: Internally, off: Externally
■ Related Parameter
Input type (initial setting level): Page 146
Unit
Default
3
Alarm 1 must be assigned.
Input type must be thermocouple or
infrared temperature sensor
Section 5-7
Default
off
Default
on