Omron E5CN User Manual page 186

Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Advanced Function Setting Level
hbl
Heater Burnout Latch
Function
Setting
See
See
hbh
Heater Burnout Hysteresis
Function
Setting
See
See
164
• When this parameter is set to ON, the heater burnout alarm is held until
either of the following conditions is satisfied.
a
Heater burnout detection is set to 0.0 A.
b
The power is turned OFF then back ON again (i.e., power is reset).
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Setting range
on: Enabled, off: Disabled
■ Related Parameter
HB ON/OFF (advanced function setting level): Page 163
• This parameter sets hysteresis for heater burnout detection.
Setting range
0.1 to 50.0
A
■ Related Parameter
HB ON/OFF (advanced function setting level): Page 163
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The "heater burnout detection"
parameter must be set to ON.
The "heater burnout" parameter must
be set to ON.
The "heater burnout latch" parameter
must be set to OFF.
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
Unit
Default
0.1
Section 5-7
Default
off