Omron E5AN Instruction Manual
Omron E5AN Instruction Manual

Omron E5AN Instruction Manual

Temperature controller
Hide thumbs Also See for E5AN:

Advertisement

Quick Links

E5AN
Temperature controller
EN
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5AN Digital Temper-
ature Controller. This manual describes the functions, perfor-
mance, and application methods needed for optimum use of
the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with
a knowledge of electrical systems.
• Before using the product, thoroughly read and understand
this manual to ensure correct use.
• Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
For detailed operating instructions, please refer to
the E5CN/AN/EN User's Manual (Cat. No.H134).
Significance of WARNINGs and CAUTIONs
Safety Precautions
●Key to Warning Symbols
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
CAUTION
carefully before using the product.
1618529-3B
AN1
■Wiring
●Dimensions
1 1. 5
8 4. 5
Dimensions (mm)
7 8
3 1
LM1
2
LM2
PV
3 2
LM3
3
H
3 3
4
SV
3 4
OUT1 STOP
5
OUT2 CMW M NU
3 5
3 6
3 7
3 8
10
Watertight
Adapter
Terminal
packing
cover
* When drawing out from its case, press down the hook and turn a screwdriver to loosen the screw on the lower part
of the front panel.
* A Setup Tool port is provided on the bottom of the product. Use this port to connect a personal computer to the
product when using the Setup Tool. E58-CIFQ1 USB-Serial Conversion Cable is required to connect the personal
computer to the product. (Do not use the product with the USB-Serial Conversion Cable left permanently
connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
●Names of parts on front panel
• Level key
Use this key to change levels:
LM1
LM2
• Press the   key and the M key
LM3
H
together for at least 3 seconds to switch
to protect level .
OUT1 STOP
OUT2 CMW M NU
• Mode key
Press this key to change the contents of
the display.
Press this button for 1 s or longer for
reverse scroll.
■Operation menu
●Input type
Setting range
Input type
Input
Setting
0
–200 to 850(℃)
Platinum
Pt100
1
–199.9 to 500.0(℃)
resistance
2
0.0 to 100.0(℃)
thermometer
3
–199.9 to 500.0(℃)
JPt100
4
0.0 to 100.0(℃)
5
K
–200 to 1300(℃)
6
–20.0 to 500.0(℃)
Thermocouple
7
–100 to 850(℃)
J
8
–20.0 to 400.0(℃)
T
9
–200 to 400(℃)
10
–199.9 to 400.0(℃)
11
0 to 600(℃)
E
L
12
–100 to 850(℃)
13
–200 to 400(℃)
U
14
–199.9 to 400.0(℃)
N
15
–200 to 1300(℃)
16
0 to 1700(℃)
R
17
0 to 1700(℃)
S
B
18
100 to 1800(℃)
Infrared
10 –70℃
19
0 to 90(℃)
20
0 to 120(℃)
Thermosensor
60 –120℃
ES1B
115 –165℃
21
0 to 165(℃)
140 –260℃
22
0 to 260(℃)
23
Use the following ranges for scaling: –1999 to 9999,
Analog input
0 to 50mV
–199.9 to 999.9, Vary Depending on "L", "H" value
• The default is "5".
• s.err will be display when a platinum resistance thermometer is mistakenly connected while input
type is not set for it. To clear the s.err display, correct the wiring and cycle the power supply.
Input type
Input
Setting
Setting range
4 to 20mA
0
Current input
Use the following ranges for scaling: –1999
0 to 20mA
1
to 9999, –199.9 to 999.9, –19.99 to 99.99,
1 to 5V
2
–1.999 to 9.999
Voltage input
0 to 5V
3
0 to 10V
4
• The default is "0".
●Alarms
Alarm output function
Alarm type
Setting
Positive alarm value (X)
0
No alarm function
Output off
L H
*1
1
Deviation upper/lower limit
ON
OFF
SP
X
2
Deviation upper limit
ON
OFF
SP
X
3
ON
Deviation lower limit
OFF
SP
L H
*1
4
ON
Deviation upper/lower range
OFF
SP
L H
Deviation upper/lower limit
*1
5
ON
standby sequence ON
OFF
SP
X
Deviation upper limit
6
ON
standby sequence ON
OFF
SP
X
Deviation lower limit
7
ON
standby sequence ON
OFF
SP
X
ON
8
Absolute value upper limit
OFF
0
X
9
ON
Absolute value lower limit
OFF
0
Absolute value upper limit
X
10
ON
standby sequence ON
OFF
0
Absolute value lower limit
X
11
ON
standby sequence ON
OFF
0
12
LBA (only for alarm 1)
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter "L" and "H".
• The default is "2".
●Error display (trouble shooting)
When an error has occurred, the No.1 display shows the error code. Take
necessary measure according to the error code, referring the table bellow.
No.1 display
Meaning
Action
Check the wiring of inputs, disconnections, shorts
Input error
and input type.
*2
s.err
After the correction of input error, turn the power OFF
(S. Err)
then back ON again. If the display remains the same,
A/D converter error
the controller must be repaired. If the display is restored
to normal, then a probable cause can be external noise
*2
affecting the control system. Check for external noise.
Turn the power OFF then back ON again. If the display
remains the same, the controller must be repaired. If the
e111
Memory error
(E111)
display is restored to normal, then a probable cause can
be external noise affecting the control system. Check for
external noise.
Internal circuit error
h.err
(H. Err)
*2
If the input value exceeds the display limit (–1999 to 9999), though it is within the control range, [[[[ will
be displayed under –1999 and ]]]] above 9999. Under these conditions, control output and alarm
output will operate normally.
Refer to "E5CN/AN/EN User's Manual" for details of control range.
*2: Error shown only for"Process value / Set point". Not shown for other status.
●Warning Symbols
CAUTION
Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to enter
the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that
does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always
consider the application conditions and use the output relays within their rated load and electrical life expectancy.
The life expectancy of output relays varies considerably with the output load and switching conditions.
Tighten the terminal screws to between 1.13 and 1.36 N•m. Loose screws may occasionally result in fire.
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable,
unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Temperature Controller may occasionally make control operations impossible or prevent alarm
outputs, resulting in property damage. To maintain safety in the event of malfunction of the Temperature Controller,
take appropriate safety measures, such as installing a monitoring device on a separate line.
A semiconductor is used in the output section of long-life relays. If excessive noise or surge is impressed on the
output terminals, a short-circuit failure is likely to occur. If the output remains shorted, fire will occur due to
overheating of the heater or other cause.
Take measures in the overall system to prevent excessive temperature increase and to prevent fire from spreading.
Suitability for Use
OMRON shall not be responsible for conformity with any standards, codes, or regulations that
apply to the combination of the products in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines,
and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE
OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT
OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.
●Installation
In the pack:
Individual mounting (mm)
• Main unit
+0.8
92
• Watertight packing
 0
• Adapter
• Instruction manual
21
1 1
22
1 2
• Terminal cover
23
1 3
(E5AN-□-500 only)
24
1 4
25
1 5
Solderless terminal size: M3.5
26
1 6
27
1 7
Terminal cover:E53-COV11
28
1 8
29
1 9
USB-Serial Conversion Cable
30
20
(Sold Separately)
(E58-CIFQ1)
• No.1 display
Process value or set data symbol
PV
• No.2 display
Set point, set data read-out value or changed
SV
input value
• Up and Down keys
Use the keys to change the values displayed on
the No.2 display.
Each press of U key increments or advances the
values displayed on the No.2 display.
Each press of D key decrements or returns the
values displayed on the No.2 display.
●Initial setting level
Operation stopped.(control/alarm are both stopped.)
/–300 to 1500(
F)
/–199.9 to 900.0(
F)
in-t
*3
/0.0 to 210.0(
Input type
F)
5
/–199.9 to 900.0(
F)
/0.0 to 210.0(
F)
/–300 to 2300(
in-h
F)
Scaling upper limit
*6
/0.0 to 900.0(
F)
(only when setting analog input)
100
/–100 to 1500(
F)
/0.0 to 750.0(
F)
in-l
Scaling lower limit
/–300 to 700(
F)
*6
(only when setting analog input)
/–199.9 to 700.0 (
F)
0
/0 to 1100(
F)
/–100 to 1500(
F)
dp
Decimal point
/–300 to 700(
F)
*6
(only when setting analog input)
0
/–199.9 to 700.0 (
F)
/–300 to 2300(
F)
°C=
c
°C/°F selection
/0 to 3000(
F)
d-u
f
°F=
*6
/0 to 3000(
F)
c
(C stands for Celsius, F for Fahrenheit)
/300 to 3200(
F)
/0 to 190(
F)
sl-h
/0 to 240(
F)
Set point upper limit
/0 to 320(
F)
1300
/0 to 500(
F)
sl-l
Set point lower limit
-200
onof
In ON/OFF control =
cntl
onof
pid
In 2-PID control =
Standard control =
s-hc
Heating and cooling control =
stnd
(Select standard control or heating
and cooling control as required)
on
st
Self-tuning ON =
*6
off
on
Self-tuning OFF =
ptrn
Program pattern
Negative alarm value (X)
off
cp
*6
Control period (heat)
20
(Unit: Seconds)
Vary with "L", "H" values
c-cp
Control period (cool)
X
*6
ON
(Unit: Seconds)
20
OFF
SP
X
orev
ON
In Reverse operation(heat) =
OFF
or-r
In Direct operation(cool) =
SP
Vary with "L", "H" values
alt1
*6
Alarm 1 type: Specified models only
2
Vary with "L", "H" values
alt2
*6
X
Alarm 2 type: Specified models only
2
ON
OFF
SP
X
alt3
ON
*6
Alarm 3 type: Specified models only
OFF
2
SP
X
ON
tr-t
OFF
Transfer output type
0
*6
off
X
ON
OFF
0
tr-h
Transfer output upper limit
*6
X
100.0
ON
OFF
0
tr-l
X
Transfer output lower limit
ON
*6
0.0
OFF
0
o1-t
Linear output type
*6
4-20
Initial setting level enables users to specify their prefer-
red operating conditions (input type, alarm type, control
method, etc.)
*3:Refer to the adjoining tables for details of input types and alarm types.
*4:Applicable only to models with alarm functions.
*5:Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items may not be displayed according to the
Status at error
models and setting.
Control
Alarm
*7: This function is supported only by models with heater burnout detection.
output
Operates
OFF
as above the
upper limit.
OFF
OFF
OFF
OFF
OFF
OFF
■Other functions
In addition to the aforementioned, there are alarm hysteresis, automatic return of
display mode and others in the advanced setting level.
Refer to
"E5CN/AN/EN
User's Manual" for details.
For communications details, please refer to
Manual".
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events.
(1) The product is designed for indoor use only. Do not use the product outdoors or in any of the following
locations.
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the
terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to a cross-
sectional area of 0.205 to 2.081 mm
type, or two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high-frequency
or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring
with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or
relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the power
before starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as a
disconnecting means for this unit.
(13) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply
shock to the terminals or electronic components. When inserting the interior of the product, do not allow the
electronic components to touch the case.
(14) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol.
(15) Design system (control panel, etc) considering the 2 second of delay that the controller's output to be set after
power ON.
(16) The output may turn OFF when shifting to certain levels. Take this into consideration when performing control.
(17) The number of EEPROM write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
(18) The product's Setup Tool port and communications terminals are internally connected in models with
communications functions. Stop transmission from communications terminals before using the Setup Tool port.
(19) Refer to the instruction sheet for installing Option unit (E53-AKB/E53-EN01/E53-EN03).
Side-by-side mounting (mm)
( 96xnumber of units–3.5 )
+1
 0
Waterproofing is impossi-
ble with side-by-side in-
stallation. When water-
proofing is required, fit
watertight packing on the
backside of front panel.
• Insert the main unit through the mounting hole in the panel (1-8 mm
thickness). Insert the mounting brackets (supplied) into the fixing
slots located on the top and bottom of the rear case.
• Alternately tighten the top and bottom screws on the mounting fixtures
applying equal pressure a little at a time until the rachet rotates freely.
• When more than one machine is installed, make sure that the ambi-
ent temperature does not exceed the specified limit.
Operation indicators
• ALM1: Alarm 1 indicator
Lit when alarm 1 is ON.
• ALM2: Alarm 2 indicator
Lit when alarm 2 is ON.
• ALM3: Alarm 3 indicator
Lit when alarm 3 is ON.
• HA: Heater burnout alarm/HS alarm indicator
Lit when a heater burnout or HS alarm has
occurred.
• OUT1: Control output 1 indicator
Lit when control output 1 is ON and not lit
when it's OFF.
For a current output, lit except for a 0% out-
put.
The setting data for the E5AN-□3HT/L is shown here
as an example.
*5
●Operation level
25
PV/SP
0
sp-m
Set point during
*6
SP ramp
0
Hold   down
Heater Current 1
ct1
for at least
*6
Value Monitor
0.0
3 seconds
(Unit: A)
(No.1display flushes,
Leakage Current 1
lcr1
then the control stops.)
*6
Value Monitor
0.0
(Unit: A)
Hold   down
prst
*6
Program start
for at least
rset
1 second
sktr
*6
Soak time remain
0
Run/Stop
r-s
*6
When control start =
run
stnd
When control stop =
h-c
al-1
*6
Alarm value 1
0
al1h
*6
Alarm value upper limit 1
0
al1l
*6
Alarm value lower limit 1
0
al-2
*6
Alarm value 2
0
al2h
*6
Alarm value upper limit 2
0
or-r
or-d
al2l
*6
Alarm value lower limit 2
0
*3
*4
al-3
*6
Alarm value 3
0
*3
*4
al3h
*6
Alarm value upper limit 3
0
*3
*4
al3l
*6
Alarm value lower limit 3
0
Operation level should normally
be used during operations.
Hold   and M keys
down for at least 1 second
●Protect level
oapt
Operation / adjustment
protect
0
icpt
Initial /
protect
1
wtpt
Setting change protect
off
prlp
Move to protect level
0
Restricts which settings can be displayed
or changed, and restricts change by key
operation.
●AT (auto-tuning)
• AT in Adjustment level
 Designate "on: AT execute" to execute
 AT and "off: AT cancel" to cancel AT.
"AT execute"
at
U
off
D
"AT cancel"
Also when AT execution ends, the display
"E5CN/AN/EN
communications User's
automatically returns to "off".
Precautions for Safe Use
2
). (The stripping length is 5 to 6 mm.). Up to two wires of same size and
●Connections
(The applicability of the electric terminals varies with the type of machine.)
•100-240V AC Type
1
11
•24V AC/DC Type
Input power supply
(no polarity)
2
12
•Relay output
•Voltage output
3
13
250V AC 5A
12V DC 40mA
Control output 1
(resistive load)
•Current output
4
14
DC4-20mA
DC0-20mA
5
15
load 600Ω max.
Alarm 3
6
1 6
Alarm output
7
1 7
(relay output)
Alarm 2
250V AC 3A
8
1 8
(resistive load)
Alarm 1. HBA/
9
1 9
HSA. input error
10
• Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output
terminals must be left unearthed when using an earthed thermocouple thermometer. (Connection makes measurements unreliable
due to sneak currents.) Basic insulation is provided between the voltage outputs (control output 2) and internal circuits.
• The last character of the lot number "R" indicates that reinforced insulation is provided between input power supply, relay outputs,
and between other terminals.
• Consult your OMRON sales representative about using the ES1B Infrared Thermosensor's external power supply for other
purposes.
• OUT2: Control output 2 indicator
Lit when control output 2 is ON and
not lit when it's OFF.
• STOP: control stop indicator
Lit when event input or "Run/Stop" is
stopped during operation.
LM1
During control stop, functions other
LM2
LM3
than control output are valid.
H
• CMW: communications writing enable/
OUT1 STOP
disable indicator
OUT2 CMW M NU
Lit when communications writing is
"enabled" and is out when it is
"disabled".
●Adjustment level
POWER ON
Only the value set to the "ins: temperature input shift" parameter is
applied to the entire temperature input range. When the process value is
200 °C, the process value is treated as 201.2 °C after input shift if the
input shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift if the input shift
value is set to –1.2 °C.
l.adj
Adjustment level
at
AT execute =
*6
off
AT cancel =
Press  
Heater Current 1
ct1
(less than
*6
Value Monitor
*7
0.0
(Unit: A)
1 second)
Leakage Current 1
lcr1
*6
Value Monitor
*7
0.0
(Unit: A)
Heater Burnout
hb1
*6
Detection 1
0.0
(Unit: A)
hs1
HS Alarm 1
*6
50.0
(Unit: A)
run
ins
Temperature input shift
*6
stop
(Unit:°C or °F)
0.0
insh
Input shift upper limit
*4
*6
when 2 point input shift
0.0
is selected
Input shift lower limit
insl
*6
when 2 point input shift
*4
0.0
is selected
p
*6
Proportional band
*4
8.0
i
*4
Integral time
*6
(Unit: secs)
233
*4
●Protection function
*4
Protection function, to prevent unwanted settings, restricts the setting items to be used
───────────────────────────────────────
or designates if operation of the key is valid or invalid.
────────────────────────
*4
●Operation / Adjustment protection
The following table shows the relationship between settings and protect limits related to
Operation level and Adjustment level.
*4
Level
Process value
*4
Operation level
PV/SP
Others
Adjustment level
●Initial setting/Communications protection
Hold   and M keys
This protect level restricts movement to the initial setting level,
down for at least
communications setting level and advanced function setting level.
3 seconds
Initial setting
Set value
level
0
1
2
×
Communication
●Setting change protection
Setting changes by key operation are restricted.
OFF "off": Setting can be changed by key operation
ON "on"
: Setting cannot be changed by key operation ("
(Protect level settings can all be changed.)
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
Telephone Consultation 1-800-55-OMRON
FAX 1-847-843-7787
OMRON EUROPE B.V.
Wegalaan 67-69 P.O. BOX 13 2130 AA Hoofddorp The
Netherlands
Phone 31-23-56-81-300
FAX 31-23-56-81-388
"at" flashes
OMRON ASIA PACIFIC PTE LTD
83 Clemenceau Avenue, #11-01 UE Square, Singapore
at
239920
on
Phone 65-6-835-3011
FAX 65-6-835-2711
●Specifications
Power supply voltage
100-240VAC type
24V AC/DC type
Operating frequency
50-60Hz
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Approx. 10VA (AC100-240V)
Approx. 5.5VA (AC24V)
Approx. 4W (DC24V)
Indication accuracy
Thermocouple, platinum resistance
(Ambient temperature: 23°C) thermometer:
(±0.5 % of indication value or ±1°C,
which is greater) ±1 digit max.
Analog input:
±0.5 % FS ±1 digit max.
Event input
output current: approx. 7 mA per contact.
Contact input
ON:1 kΩ max., OFF: 100 kΩ min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Control output 1
Relay output: SPST-NO,
250 VAC, 5A(resistive load)
Voltage output: 12 VDC, 40 mA
Current output: 4 to 20 mA DC, 0 to 20 mA DC
load: 600 Ω max.
Electrical life of relay:
100,000 operations
Control output 2
Voltage output: 12 VDC, 21 mA
Relay output: SPST-NO,
250 VAC, 3A(resistive load)
Electrical life of relay:
1 million operations (Long-life model)
External power supply for ES1B 12 VDC±10% at 20mA
Control method
ON/OFF or 2-PID control
Alarm output
Relay output: SPST-NO, 250 VAC,
3 A(resistive load),
electrical life: 100,000 operations
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
RH 25 to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000m
Recommended fuse
T2A, 250V AC, time-lag,
low-breaking capacity
Weight
Approx. 310g (main unit only)
Degree of protection
Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IP20, Terminal section: IP00
Installation environment
Installation category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
EEPROM (non-volatile memory)
(Number of write operations: 1,000,000)
Event Inputs
RS-232C
RS-485
SD
B (+)
E V 2
E V 1
RD
A (–)
CT input
SG
Do not use
•1 point
•2 points
•Long-life
•External power supply
relay output
•Voltage output:
Control output 2
for ES1B
CT1
CT1
250V AC 3A
12V DC 21 mA
12V DC 20mA
(resistive load)
A
+
mA
CT2
B
V
CTs: E54-CT1 or E54-CT3
B
+
+
(available separately)
TC/Pt multi-input
Analog input
• °C / °F : temperature unit
The temperature unit is displayed
when the displayed value is a
temperature.
When this parameter is set to "°C",
"C" is displayed, and when set to
"°F", "F" is displayed.
PV
This flashes while ST(Self-Tuning) is
activated.
SV
: Protection indicator
Lit when Setting Change Protect is
ON (disables the Up and Down Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is set
to Manual Mode.
*6
d
Derivative time
40
(Unit: secs)
on
c-sc
Cooling coefficient
*6
off
1.00
c-db
Dead band
*6
0.0
*7
of-r
Manual reset value
*6
(Unit: %)
50.0
*7
hys
Hysteresis
*6
1.0
(heat)
*7
chys
Hysteresis
*6
*7
(cool)
1.0
soak
*6
Soak time
1
wt-b
*6
Wait band
off
sprt
*6
SP ramp set value
off
ol-h
MV upper limit
*6
105.0
ol-l
*6
MV lower limit
-5.0
Adjustment level is for entering set values
and shift values for control.
◎:Can be displayed and changed
Set value
○:Can be displayed
2
3
0
1
×:Display or shifting to another level
is not possible.
×
×
×
×
×
Default setting : 0
○:Change to
Communications
Advanced function
other levels
setting level
setting level
possible
×:Change to
other levels
×
not possible
×
×
Default setting : 1
" will light.)

Advertisement

loading

Summary of Contents for Omron E5AN

  • Page 1 Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods. and between other terminals. • Consult your OMRON sales representative about using the ES1B Infrared Thermosensor's external power supply for other ●Names of parts on front panel purposes.
  • Page 2 ・OUT1:制御出力1表示 します。 時に3秒以上押すと、プロテクトレ ・CMW:通信による書き込み可否表示  制御出力1機能がONのとき点灯、OFFのと ます。または設定内容が進みます。 き消灯します。  通信書込が許可(ON)で点灯、禁止  ・MANU:マニュアル出力表示 ベルに切り替わります。  Dキーを押すごとに、第2表示の値がダウンし 電流出力の場合は、0%出力以外で点灯しま (OFF)で消灯します。 「オート/マニュアルモード」がマニュアルモー す。 ます。または設定内容が戻ります。 ドで点灯します。 ■操作メニュー 使用例と してE5AN-□3HT/Lについての設定デ−タ を 運転が停止します。 (制御・警報共に停止) ●入力種別 ●初期設定レベル 示しています。 「ins」温度入力補正値の設定値分だけ、センサ入力範囲のすべての点において ●調整レベル 入力温度を補正します。補正前の現在値が200℃のとき、補正値を1.2℃とする *5 設定範囲 入力種別 仕様 設定値 と補正後は201.2℃、補正値を-1.2℃とすると補正後は198.8℃として扱います。 電 源 投 入 −200∼850(℃)...