Shifting Input Values

4-1

Shifting Input Values

4-1-1

Shifting Inputs

One-point shift
Temperature
ins
input shift
Operating Procedure
Operation Level
C
30
200
Adjustment Level
Adjustment level
l.adj
display
Temperature
C
ins
input shift
0.0
C
ins
1.0
Operation Level
C
31
200
The input shift matched to the sensor currently selected in the "input type"
parameter is displayed.
• A 2-point shift is applied for infrared temperature sensors. A 2-point shift
can also be used if the "input shift type" parameter (advanced function
setting level) is set to INS2 for a thermocouple or platinum resistance
thermometer.
• With a 1-point shift, the value set for the "temperature input shift" parame-
ter (adjustment level) is applied to each point in the entire temperature
input range. For example, if the input shift value is set to 1.2 C, the pro-
cess value is treated as 201.2 C after the input shift is applied when the
measured process value is 200 C.
Temperature
Upper limit
After shifting
Input shift value
Lower limit
0
In this example, the input from a K sensor is shifted by 1 C using a 1-point
input shift.
Operation Level
1. Press the O key to move from the operation level to the adjustment level.
2. Select the "temperature input shift" parameter by pressing the M key.
3. Press the U or D key to set 1.0.
4. To return to the operation level, press the O key. The process value is
1 C larger than before the shift was applied.
Before
shifting
Input
100
Section 4-1
67