Omron E5CN User Manual page 130

Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Using the Simple Program Function
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input type
in-t
5
Initial Setting Level
Program Pattern
ptrn
off
ptrn
stop
Operation Level
PV/SP
C
25
100
Adjustment Level
Adjustment level
l.adj
display
Adjustment Level
Soak time
soak
1
soak
10
Adjustment Level
Wait band
wt-b
off
wt-b
3.0
Operation Level
PV/SP
C
25
100
108
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the "program pattern" parameter by pressing the M key.
3. Use the U key to set the parameter to STOP.
4. Press the O key for at least one second to move from the initial setting
level to the operation level.
5. Press the O key to move from the operation level to the adjustment level.
6. Select the "soak time" parameter by pressing the M key.
7. Use the U key to set the parameter to 10. (The soak time unit is set in
"soak time unit" parameter in the advance function setting level. The de-
fault is m (minutes).
8. Select the "wait band" parameter by pressing the M key.
9. Use the U key to set the parameter to 3.0.
10. Press the O key to move from the adjustment level to the operation level.
Section 4-15