Advanced Function Setting Level
lba
LBA Detection Time
Function
Setting
See
See
lbal
LBA Level
Function
Setting
Note
See
See
176
This parameter enables or disables the LBA function and sets the detection
time interval.
• Set the time interval for detecting loop burnouts.
• To disable the LBA function, set 0.
Setting range
0 to 9999
Second
■ Related Parameters
Alarm 1 type (initial setting level): Page 152
LBA level: Page 176, LBA band: Page 177 (advanced function setting level)
• This parameter sets the LBA level.
• If the deviation between the SP and PV exceeds the LBA level, a loop
burnout is detected.
Models
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
Controllers with Analog Inputs
Set "none" as the unit for Controllers with Analog Inputs.
■ Related Parameters
Process value/set point (operation level): Page 120
Alarm 1 type (initial setting level): Page 152
LBA detection time: Page 176, LBA band: Page 177 (advanced function set-
ting level)
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
Unit
Default
0
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
Setting range
0.1 to 999.9
0.01 to 99.99
Section 5-7
Unit
Default
C or F
8.0
(See note.)
%FS
10.00