Omron E5CN User Manual page 125

Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Using the Transfer Output
Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input type
in-t
5
Initial Setting Level
Transfer output
tr-t
type
off
tr-t
sp
Initial Setting Level
Transfer output
C
tr-h
upper limit
1300
C
tr-h
200
Initial Setting Level
Transfer output
C
tr-l
lower limit
-200
C
tr-l
-50
Operation Level
PV/SP
C
25
100
The following procedure sets the transfer output for an SP range of 50 to
200.
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the "transfer output type" parameter by pressing the M key.
3. Press the U key to select sp (set point).
4. Select the "transfer output upper limit" parameter by pressing the M key.
5. Use the D key to set the parameter to 200. The default is 1300.
6. Select the "transfer output lower limit" parameter by pressing the M key.
7. Use the U key to set the parameter to 50. The default is 200.
8. To return to the operation level, press the O key for at least one second.
Section 4-14