Operation Level
sp-m
Set Point During SP Ramp
Function
Monitor
See
See
ct1
Heater Current 1 Value Monitor
Function
Monitor
See
See
This parameter monitors the set point during SP ramp operation.
A ramp is used to restrict the change width of the set point as a rate of
change.
This parameter is displayed when a set value is input for the "SP ramp set
value" (adjustment level).
When not in ramp operation, the set point will be the same as the one dis-
played for the "process value/set point" parameter.
Monitor range
SP: SP lower limit to SP upper limit
■ Related Parameters
Process value/set point (operation level): Page 120
SP ramp set value (adjustment level): Page 143
Set point upper limit, Set point lower limit (initial setting level): Page 149
This parameter measures the heater current from the CT input used for
detecting heater burnout.
This parameter measures and displays the heater current value.
• Heater burnouts are not detected if the control output (heating) ON time is
190 ms or less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If a heater burnout is detected, the HA indicator will light, and the relative
setting level will flash on the No. 1 display.
■ Related Parameters
Heater burnout detection 1, Heater burnout detection 2 (adjustment level):
Page 134
Heater burnout (advanced function setting level): Page 163
Error Displays ct1: Page 206
The "SP ramp set value" parameter
must not be set to OFF.
The "ST" parameter must be set to
OFF.
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The "heater burnout detection"
parameter must be set to ON.
Unit
A
Section 5-3
Unit
EU