Communications Function

1-4
Communications Function
1,2,3...
Note
• When you turn the power OFF, you must first fix the settings (by pressing
the M key). The settings are sometimes not changed by merely pressing
the U or D keys.
The E5CN/AN/EN is provided with a communications function that enables
parameters to be checked and set from a host computer. If the communica-
tions function is required, use a model that has that function (E5@N-@@@03
and E5AN/EN-@@@01). For details on the communications function, see the
separate Communications Functions User's Manual. Use the following proce-
dure to move to the communications setting level.
1. Press the O key for at least three seconds to move from the operation level
to the initial setting level.
2. Press the O key for less than one second to move from the initial setting
level to the communications setting level.
3. Select the parameters as shown below by pressing the M key.
4. Press the U or D key to change the parameter setting.
psel
Protocol setting
cwf
M
u-no
Communications Unit No.
1
M
Communications baud rate
bps
9.6
M
Communications data length
len
(See note.)
7
M
sbit
Communications stop bits
(See note.)
2
M
prty
Communications parity
even
M
Send data wait time
sdwt
20
M
The "protocol setting" parameter is displayed only when CompoWay/F com-
munications are being used.