Omron E5CN User Manual page 242

Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Input type
Control-
Current input
lers with
Analog
Voltage input
Inputs
• The default is 5 ( C/ F) for Controllers with Thermocouple/Resistance Thermometer Multi-Inputs and 0 for
Controllers with Analog Inputs.
• The applicable standards for each of the above input ranges are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1
L:
U:
JPt100:
Pt100:
Control Range
• Resistance thermometer and thermocouple input
Temperature lower limit
temperature upper limit + 40 C
• ES1B input:
Same as input indication range
• Analog input
5% to +105% of scaling range
220
Specifications
Set value
4 to 20 mA
0
0 to 20 mA
1
1 to 5 V
2
0 to 5 V
3
0 to 10 V
4
Fe-CuNi, DIN 43710-1985
Cu-CuNi, DIN 43710-1985
JIS C 1604-1989, JIS C 1606-1989
JIS C 1604-1997, IEC 751
20 C to temperature upper limit + 20 C, or temperature lower limit
Input temperature range
Any of the following ranges,
by scaling:
1,999 to 9,999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
Appendix A
Input indication range
5% to 105% of setting
range. The display shows
1999 to 9999 (numeric
range with decimal point
omitted).
40 C to

Hide quick links: