Advanced Function Setting Level
See
See
spru
SP Ramp Time Unit
Function
Setting
See
See
rest
Standby Sequence Reset
Function
Setting
■ Related Parameters
Multi-SP set point setting (operation level): Page 120
Number of multi-SP uses (advanced function setting level): Page 159
• This parameter sets the time unit for the rate of change during SP ramp
operation.
Setting range
s: EU/s, m: EU/min
■ Related Parameters
Ramp SP monitor (operation level): Page 121
SP ramp set value (adjustment level): Page 143
• This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
• Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
• Condition B
Power ON
• The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Alarm
(after change)
Alarm
Alarm output:
Condition A
Alarm output:
Condition B
Setting range
a: Condition A, b: Condition B
The "ST" parameter must be set to
OFF.
m
The alarm 1/2/3 type must be set to
a type with a standby sequence.
Condition A only
SP change
Condition A
only
a
Section 5-7
Default
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Default
161