Advanced Function Setting Level
ev-m
Number of Multi-SP Uses
Function
Setting
Note
Multi-SP is a function for setting set points 0 to 3 in advance, and switching
between these set points using the ON/OFF combinations of event inputs 1
and 2.
The "number of multi-SP uses" parameter is used when the number of preset
set points is either two or four.
This parameter determines whether the "event input assignment 1" and "event
input assignment 2" parameters are displayed.
The "number of multi-SP uses" parameter displays which functions are
assigned to event inputs 1 and 2.
Event input
assignment 1
Number of
0 (See
NONE, STOP, MANU, PRST
multi-SP
note
(See note 2.)
uses
1.)
1
(Not dis-
played.)
2
(Not displayed.)
(1) If the "number of multi-SP uses" parameter is set to 0, both input assign-
ments 1 and 2 can be set. Once "STOP" (RUN/STOP), "MANU" (auto/
manual), or "PRST" (program start) has been assigned to one event in-
put, the other event can be assigned only to either of the remaining two
settings.
(2) "PRST" (program start) can be set only when the "program pattern" pa-
rameter has not be set to OFF.
If the "program pattern" parameter is set to OFF (i.e., if the simple pro-
gram mode is not selected) when "PRST" (program start) is set, the as-
signment of the input will automatically be changed to "NONE."
• Default: 1
Multi-SP switching by event inputs can be used with Controllers that have
event inputs, when the "number of multi-SP uses" parameter is set to 1 or 2.
The following tables show the relationships between ON/OFF combinations of
event inputs 1 and 2 and selected set points.
Number of Multi-SP Uses: 1
Event input 1
OFF
Set point 0
ON
Set point 1
Number of Multi-SP Uses: 2
Event input 1
OFF
OFF
ON
OFF
Event inputs must be supported.
Settings
Event input
assignment 2
NONE, STOP,
MANU, PRST
(See note 2.)
Selected set point
Event input 2
Selected set point
Set point 0
Set point 1
Section 5-7
Event inputs
Function of
Function of
event input 1
event input 2
None, or switching RUN/
STOP, auto/manual, or pro-
gram starts
Multi-SP, 2
None, or
points (switch-
switching
ing set points
RUN/STOP,
0 and 1)
auto/manual,
or program
starts
Multi-SP, 4 points (switching
set points 0, 1, 2, 3)
159