68 Modbus/TCP – Start-up
Parameter setting examples – ACS355
Speed and torque control using the ABB Drives –
Enhanced communication profile
This example shows how to configure a speed and torque control
application that uses the ABB Drives - Enhanced profile. In
addition, some application-specific data is added to the
communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
communication profile
When Reference 1 (REF1) is used, a reference value of ±20000
(decimal) corresponds to the reference set with parameter 1105
REF1 MAX in the forward and reverse directions.
When Reference 2 (REF2) is used, a reference value of ±10000
(decimal) corresponds to the reference set with parameter 1108
REF2 MAX in the forward and reverse directions.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
Output data
Control word
Speed reference
Torque reference
1)
Constant speed 1
1)
Constant speed 2
1)
Example
The table below gives the recommended drive parameter settings.
Drive parameter
9802 COMM PROT SEL
5101 FBA TYPE
on page 91.
Modbus
Input data
register
(4)00001
Status word
(4)00002
Speed actual value
(4)00003
Torque actual value
(4)00004
Power
(4)00005
DC bus voltage
Setting for ACS355
drives
4 = EXT FBA
1)
ETHERNET
ABB Drives
Modbus
register
(4)00051
(4)00052
(4)00053
1)
(4)00054
1)
(4)00055
Description
Enables communication
between the drive and the
fieldbus adapter module.
Displays the type of the fieldbus
adapter module.