36 Start-up

Activating drive control functions with ACH580

Drive control

To enable fieldbus control of various drive functions through
BACnet/IP, do the following:
configure the drive to accept fieldbus control of the function.
define a fieldbus input for any drive data required for fieldbus
control.
define a fieldbus output for any control data required by the
drive.
See the individual control functions described in below sections
with details of configuration.
Note: Change only those parameter of the functions that you want
to control through BACnet/IP. All other parameters should remain
as factory default values.
For a complete parameter list, see the relevant drives manual.

Start/stop direction control

For Start/stop direction control through fieldbus, configure the
following drive parameters and set the fieldbus controller supplied
command(s) in the appropriate location:
Drive parameter
20.01 Ext1
commands
20.06 Ext2
commands
20.21 Direction
Value
Description
Fieldbus A Start/stop by fieldbus
with Ext1 selected
Fieldbus A Start/stop by fieldbus
with Ext2 selected
Request
Direction by fieldbus, if
required
BACnet
access point
BV10
BV10
BV11