Parameter Setting Examples; Frequency Control - ABB FBIP-21 BACnet/IP User Manual

Table of Contents

Advertisement

Parameter setting examples

Frequency control

The table below shows an example of how to configure a basic
frequency control application. Assume the rest of parameters are
in default values.
ACH580
Drive parameter
50.01 FBA A enable
51.01 FBA A type
51.03 Commrate
51.04 IP
configuration
51.05 IP address 1
51.06 IP address 2
51.07 IP address 3
51.08 IP address 4
51.09 Subnet CIDR
51.14 Device obj ID
lo
51.20 Comm loss
time
Settings
1 = Enable
1)
47808 = BACnet
2)
0 = Auto
1 = Static IP
2)
192
2)
168
2)
0
2)
16
2)
24
2)
51
2)
300
Start-up 47
Description
Enables communication
between the drive and
fieldbus adapter A, and
specifies the slot the adapter
is installed into.
Shows the fieldbus adapter
type as detected by the
drive.
BACnet communication rate
is negotiated automatically
by the device.
Configuration is obtained
through parameter
51.05...51.13.
First part of the IP address
Second part of the IP
address
Third part of the IP address
Last part of the IP address
Sets the network mask as
255.255.255.0, allowing
access only to the last
subnet.
Configures device object ID.
Sets the communication
timeout as 30 seconds.