D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS

P### BFSK/Relay

Program Record Sheet
Default:
See
Selection:
0 to 9
Use this option to:
2. Determine the point number reported in BFSK
when this point is tripped.
Activate a relay when the point goes into an
3.
alarm condition, even if the control panel is
programmed for Modem reporting as shown in
Table 29.
BFSK/Relays do not activate for Fire
Supervisory or Non-Fire Supervisory
points.

Table 29: P### BFSK/Relay Codes/Relays

D8129 on Zonex
BFSK Code
1
2
3
4
5
6
7
8
* Address setting = 1 (on), 2 (off), 3 (on), 4 (on)
Local annunciation on the command
centers and Local Printer reporting and
the View Log display the actual point
number (1 to 247), not the BFSK report
code
0101
Do not assign a BFSK/Relay to Invisible
0101
points. To avoid triggering a BFSK/Relay,
0101
program this prompt as 0.
On the D9412G, do not use relays 73
through 80 for Area or Panel-Wide Relay
functions when using BFSK relays. Doing
so prevents the BFSK relays from
triggering.
On the D7412G, do not use relays 9
through 16 for Area or Panel Wide Relay
functions when using BFSK relays. Doing
so prevents BFSK relays from triggering.
Bosch Security Systems | 10/03 | 47775E
Trips Relay
D8129 on Zonex
Bus 2 for
Bus 2 for
D9412G*
D7412G*
73
9
74
10
75
11
76
12
77
13
78
14
79
15
80
16
Two relays can activate when this point
goes into alarm if the P## Rly Resp Type
for this point is programmed.
Use these codes to activate relays on the
D8129 OctoRelay (or C8137 Transmitter
Interface). You can assign the same code
to several points providing a summary
zone alarm output. When the point goes
into alarm, the relay activates. When the
alarm is acknowledged and is no longer
scrolling in the command center display,
the relay resets.

P### Point Text

Program Record Sheet
Default:
See
Selection:
Up to sixteen alphanumeric
characters
Enter alphabetic characters (A to Z) in capital letters.
Enter up to sixteen characters of text to describe the
point. This point text is displayed at command
centers, if the point is programmed as visible, and
reported to the D6500/D6600 when transmitting in
2
Radionics Modem IIIa
format (if it is a reporting
point).
Include the point number in custom point text. This
helps the user when viewing events, initiating
bypasses, and so on. It can also simplify
troubleshooting.
When a D1260 Command Center is
installed on the system, the point text for
Points 240 to 247 can be used for Area
Name Text for Areas 1 to 8, respectively.
See Table 30:

Table 30: Point Text for Points 240 to 247

Point Text
Corresponding Area Name Text
Point 240
Area 1
Point 241
Area 2
Point 242
Area 3
Point 243
Area 4
Point 244
Area 5
Point 245
Area 6
Point 246
Area 7
Point 247
Area 8