Multiple Zzrm Relay Installation; Conventional Zone Input Capabilities; Printer Output Options - Zeta Classic 2000 MKII Installation And Operation Manual

January 2002,part # z6000-0001 man-z3k-01 revision 1.0
Table of Contents

Advertisement

Zeta Alarm Systems.
M u l t i p l e Z Z R M R e l a y I n s t a l l a t i o n
2 . 7 . 1 . 1
ZZRM JP-1 Jumper Setup
Jumper pins 1and 2 on the ZZRM furthest from the CP3 connection. All other ZZRMs should have
the jumper on pins 2 and 3.
ZZRM Installation (refer to section 2.9 for wiring schematic)
NOTE: Up to 2 ZZRMs may be installed under the CP3 in the main enclosure (4 ZZRMs if the batter-
ies are in optional listed battery enclosure). Additional ZZRMs may be enclosed in a serial device
enclosure (ZSDE) or other listed enclosure. Remotely mounted ZZRMs must be located within 20
feet of the main panel in the same room, and connected in conduit.
* Please note that to connect 3 to 4 ZZRMs requires a special-order cable, p/n 2921.
2 . 8
C o n v e n t i o n a l Z o n e I n p u t C a p a b i l i t i e s
The control will support up to 600 conventional points via the RS-485 bus. See Section 6 – Networking/
Serial Devices and Appendix C-3 – Compatible Detectors for manufacturers and model numbers of com-
patible two-wire detectors.
See Section 3.0 for each device type's operation.
2 . 9
P r i n t e r O u t p u t O p t i o n s
The Series 3000 offers two printer output options:
1.
ZSCP3The ZSCP3 offers a standard (not isolated) RS-232 printer or PC interface. The ZSCP3
requires the use of a DB9 Female-to-Female Null Modem cable to hook up to a printer or PC.
2.
ZICP The ZICP offers an isolated RS-232 printer interface (should be used when interconnecting to
ITE listed equipment without isolated grounds to prevent ground fault problems on the S3000).
The ZICP requires the use of a DB9 Female-to-Female Straight-Through cable to hook up to a
printer or PC.
Installation instructions are included with each device. Section 1.4.7 outlines port specifications. Section
3.10 discusses the ZSCP3 / ZICP in more detail. Appendix K explains printing in depth.
Revision 1.0
Classic 2000 Mk II Operation Manual
Part # MAN-Z3K-01
Page 38