Zeta Classic 2000 MKII Installation And Operation Manual page 66

January 2002,part # z6000-0001 man-z3k-01 revision 1.0
Table of Contents

Advertisement

Zeta Alarm Systems.
4 . 2 . 6 . 2 A d d / R e m o v e P o i n t
To add an SLC point:
1. Connect the new device to the SLC and physically set an unused address for the device with
the X-pert Card for sensors, or the 8-button DIL (DIP) switch on the modules.
2. Select 6. Points from the PROG menu.
3. Select 5. Auto-Program to scan all SLC loops for the new device(s). The system will automati-
cally establish the new SLC resident(s) to their system default settings.
4. Select 1. Point: X: XXX and enter the loop number, then the address of the first new device
and press ENTER.
5. Edit the point as described in the following sections.
To remove an SLC point:
1. Physically disconnect the device from the loop. This will cause a trouble condition. Press
RESET, then PROG immediately after the panel establishes a normal condition.
2. Select 5. Auto-Program and re-scan the loop.
3. Press ESCAPE to exit the menu and RESET to return to normal operation.
NOTE: Only "changed" points are programmed, i.e., if a point is already programmed and its
device type matches the "new" device type, then it is not modified. Otherwise, the point's program-
ming is set to the default for that device type.
4 . 2 . 6 . 3 P o i n t L o c a t i o n
Once all the points have been logged using Auto-Program, to access a specific point, press 1.
Point and then enter the loop and address of the specific point to be reviewed or edited. There are
three options available for assessing each system point: Browse, Edit, Status.
4 . 2 . 6 . 4 P o i n t P r o g r a m m i n g O p t i o n s - E d i t
Once the Edit menu has been accessed, press:
1. Enable/Disable to turn a device on or off (note that a disabled device will cause a
system trouble);
2. Label to edit the 40-character label;
3. Mapping to assign or change the output group(s) associated with that point and assign
LED outputs;
4. Options to select any options available for that device type. For example, if editing a priority
monitor module you may select the type of monitor input from a pre-established set of options.
When editing a sensor, you select sensor sensitivity – high, medium, or low (and for further
sensitivity, the offset). When editing the points of a ZZRM, you can configure each relay as
silenceable or non-silenceable from this menu. In other words, the options vary per device.
See Appendix E for detailed information.