Zeta Alarm Systems.
SYSTEM COMPONENTS
Other - NAC #4, 2.75 Amps Maximum
GMS24-15/75WR
GEC24-15/75WR
TOTAL STANDBY CURRENT - mA
TOTAL ALARM CURRENT - mA
TOTALS
A) Supervisory (standby) Current - mA (Item 35, above)
B) Supervisory Time in Hours (24 or 60)
C) Supervisory Requirements (A x B)
D) Power Supply Size (Enter .00575 or .0075) or Alarm Current (Item 36, above)
E) Alarm Time in Minutes (For 5mins enter .0833; for 10mins enter .167)
F) Alarm Requirement (D x E)
G) Battery Backup Requirement (C + F)
H) 20% Safety Factor (G x .2)
I) Battery Requirement w/ 20% Safety Factor (G + H)
J) Required Battery Size in Amps.
NOTES:
1. Required for remote ZACMs
2. SLC Loops are Current Limited at 80mA in alarm. This requirement is included on the last line of the Detectors/
Modules section of this chart.
3. Review the top line for the indication of standby and alarm current
4. Current values are in mAmps unless otherwise specified.