The ZPNI may be addressed to one of 32 network addresses. Use the DIP switch on the board to
set the address.
Bit
Number
0
Network Address Bit 0
1
Network Address Bit 1
2
Network Address Bit 2
3
Network Address Bit 3
4
Network Address Bit 4
5
6
Global Silence*
7
Global Reset*
*Global Silence and Reset apply only to the ZPNI-DRV. See ZPNI product documentaion for explanation
and application.
6 . 5
S e r i a l D e v i c e T e c h n i c a l S p e c i f i c a t i o n s
POWER REQUIREMENT
To be connected to a UL listed Power Limited
Input Voltage
Normal Mode (Standby)
10% Alarm Condition
Each zone in alarm adds ...
Each ZZRM relay on adds ...
Revision 1.0
Description
Class II or Class III source of supply only
Part # MAN-Z3K-01
Classic 2000 Mk II Operation Manual
Minimum
22VDC
Nominal
24VDC
Maximum
25.5VDC
ZTZB
65mA
ZZRM
1.5mA
ZTZB (1 zone)
110mA
ZZRM (1 zone)
18mA
45mA
16mA
Page 80