Zeta Classic 2000 MKII Installation And Operation Manual page 59

January 2002,part # z6000-0001 man-z3k-01 revision 1.0
Table of Contents

Advertisement

Zeta Alarm Systems.
4 . 2 . 2 S y s t e m
The System parameters allow you to program system options by toggling between system
defaults and available options or entering numerical values. There are four menus associated with
this area of programming: Options, Timing, Access Codes, and Edit Banner Message. NOTE: This
area requires a Level Two APC to begin.
4 . 2 . 2 . 1
S y s t e m O p t i o n s
The System Options menu presents all the general system operation settings. These include trou-
ble latching operation (LatchTroubles), trouble reminder enabling (TroubleRemind), waterflow
silenceability (WaterflowSil), printer operation (Printer), and floor above/below configuration (Floor-
Config). Each menu is toggled by pressing the associated number (1, 2, 3, 4, or 5) to display the
possible options available under each menu option.
Menu Option 1 – Latch Troubles: XXX - Press 1 to select yes. A "yes" selection will cause all
trouble conditions to latch. Latching means that all trouble conditions will require the trouble to be
resolved and the system reset prior to returning the system to normal operating condition. Press 1
again to select "no" and allow a trouble-restore operation. A restore operation will return the panel
to normal operating condition when a trouble condition has cleared or resolved. Any relays not
selected for a latching operation will return to normal state, and a 'trouble-cleared' message will be
sent to the event history.
Menu Option 2 – TroubleRemind: XXX - Select yes to silence trouble conditions and provide an
audible "error" signal every 5 minutes. Subsequent new Troubles will cause trouble operation to
resound, and Silence will recycle the 5-minute trouble reminder signal.
Menu Option 3 – WaterflowSil: XXX - The panel default setting is "no" in compliance with NFPA
requirements. When "no" is selected, any alarms caused by waterflow devices monitored by this
panel will not respond to the panel's silence function. "Yes" will allow the alarm to be silenced. This
option allows compliance with some local AHJs (Authority Having Jurisdiction).
Menu Option 4 – Printer: XXX - Establishes Printer settings. "Disabled" means no printer is
installed or the output is turned off. "Manual" will output the selected items only when you select the
print menu, and "auto" will automatically send data as it occurs and is sent to the event history log.
Menu Option 5 – FloorConfig: XXXX - This setting (in concert with the "floor" parameter of each
output group) determines the operation of the panel's "floor above / floor below" function. The set-
tings are as follows: "1 Above / 1 Below" = 1A/1B; "2 Above / 1 Below" = 2A/1B; "1 Above / 2
Below" = 1A/2B; or "2 Above / 2 Below" = 2A/2B.
Revision 1.0
Figure P-9
Part # MAN-Z3K-01
Classic 2000 Mk II Operation Manual
Figure P-8
Figure P-10
Page 53