The eight DIP switch positions are assigned as follows:
Bit
Description
Number
1
Network Address, Bit 0
2
Network Address, Bit 1
3
Network Address, Bit 2
4
Network Address, Bit 3
5
Local Silence Enable
6
Global Silence Enable
7
Drill Test Function
8
Reset Enable
The ZRDA uses serial EEPROM for addressing. Approximately 15 seconds after applying power,
the ZRDA will annunciate a communication fail trouble. Pressing any button on the screen will ask
you to provide a network address from those available. The available address range for ZRDAs is
32-47. Select your address by pushing Prev/Next button until the one you want is shown. You must
then rescan the network.
To scan the loop, follow these instructions:
Select (1) for PROG
Select (3) for Network
Select (1) for Scan Network
The trouble will clear and your ZRDA will now be functioning normally. If the ZRDA address needs
to be changed, remove the network connection, wait for a "Comm Trouble", and change the
address.
Revision 1.0
Classic 2000 Mk II Operation Manual
"ON"
1
1
1
1
Allow the "Silence" switch
input to silence the ZRLD.
Allow the "Silence" switch
input to silence all devices on
the network.
1
Allow the "Reset" switch input
to reset the ZRLD and net-
work.
Part # MAN-Z3K-01
"OFF"
0
0
0
0
Don't allow the "Silence"
switch input to silence the
ZRLD.
Don't allow the "Silence"
switch input to silence all
devices on the network.
0
Don't allow the "Reset" switch
input to reset the ZRLD and
network.
Page 78